Technical - Fan Coils with MasterTherm Heat Pumps
Posted on 02 June 2017 in FAQ
When using fan coils with MasterTherm Heat Pumps, they must be based/sized on the following water design temperatures.
Heating mode: +25 to +50°c
DEAD ZONE: +20 to 25°c
Cooling mode: +20 to +6°c
The change over temperature for heating is 25°c and 20°c for cooling.
The fan coils must be based on a 2 pipe system and must have the internal water thermostat set to operate at the above temperatures. The fan coils must be equipped with internal motorised valves.